
6.4. Checking Air and Fluid Pressure
To be sure the system is functioning normally, the following
inspection sequence can be run:
· Preparation
- Position the unit on a bowling lane (see 'Mounting the
Unit onto a Bowling Lane').
- Make sure the start indicator
within the start button
burns continuously.
(If this is not the case, go to 'TROUBLE CHECKS').
- Press the illuminated green start button
. The air pump will be
switched on and after a few seconds the unit will start
moving. The start indicator
will flash.
- As soon as the unit starts moving, briefly press the
start button
to temporarily halt the conditioning session; the air
pump will stay on.
· Check Air Pressure
- Check the pressure of the atomizing air: 0.7 - 0.8 bar.
This pressure is indicated on the lower pressure gauge in
the control compartment.
- If necessary, the pressure can be regulated with the
pressure regulator next to the pressure gauge: pull the
knob, turn it and press it back.
- Check the pressure of the external air flow: 0.1 - 0.2
bar. This pressure is indicated on the upper pressure
gauge in the control compartment.
- If necessary, the pressure can be regulated in the same
manner as described at item 2.
· Check Fluid Pressure
- Disconnect the (blue) tube connected to the fastener on
the upper right hand side of the oil tank. To do this,
push the tube into the fastener, hold back the
quick-disconnect ring, then pull back the tube out of the
fastener.
- Connect the supplied pressure gauge to the loose tube
end: push the tube end firmly into the fastener of the
pressure gauge, then pull back the tube to secure the
connection.
- Check the gauge reading: 0.2 - 0.35 bar.
- If necessary, the fluid pressure can be adjusted with the
black precision pressure regulator on the regulator unit
which is located in the control compartment at the right
hand side: loosen the butterfly nut, turn the regulator
shaft, then tighten the butterfly nut. HINT:
back-trace the disconected tube to find the precision
pressure regulator.
- Connect the tube back to the fastener on the tank. As
described at item 2, press the tube firmly into the
fastener, then pull it back to secure the connection.
· Detect Leaks in Air System
- Resume the conditioning session by briefly pressing the
flashing start button
.
- Leave open the control panel and check during the full
duration of the conditioning session the pressure of the
atomizing air (lower pressure gauge). The pressure should
not fall below 0.6 bar. Also, the indicator needle may
not (start to) vibrate. If this does happen, the air
system should be checked for leakage.